Wzonpa, a professional manufacturer and supplier in China provides the 11KV Indoor vacuum Load Break Switch featuring a compact integrated structure, vacuum arc extinguishing technology, and reliable mechanical interlocking. It delivers stable switching performance, enhanced operational safety, and reduced maintenance, making it suitable for modern medium-voltage distribution systems requiring efficient and secure load control.
As a leding China manufacturer, Wzonpa delivers the 11KV Indoor vacuum Load Break Switch engineered for medium-voltage distribution systems. Designed with a compact integrated structure, this switch combines load breaking, grounding, and protection functions into a single unit, ensuring safe and efficient power control in indoor switchgear assemblies.
What is 11KV Indoor Vacuum Load Break Switch?
The 11KV Indoor vacuum Load Break Switch is a key switching device used to control, protect, and isolate electrical circuits under normal load conditions.
Core Functions
Load switching: Safely connects and disconnects rated current
Isolation: Provides visible and reliable disconnection
Arc extinction: Uses vacuum interrupter to ensure clean interruption
Safety grounding: Works with interlocking systems to prevent misoperation
Key Advantages
1.Compact Integrated Structure
Combines load switch, grounding switch, and mechanism in one frame
Reduces installation space and simplifies panel design
Prevents incorrect operation between grounding and load switch
Fully compliant with “five-prevention” safety requirements
4.Flexible Operation Modes
Supports manual and electric operation
Compatible with AC/DC auxiliary control systems
Working Principle
1.Vacuum Interruption Mechanism
Contacts separate inside sealed vacuum chamber
Arc is quickly extinguished due to high dielectric strength
2.Energy Storage Operation
Spring mechanism ensures rapid opening/closing
Independent of operator speed for consistent performance
3.Safety Interlock Logic
Grounding switch cannot close unless load switch is open
Guarantees safe maintenance conditions
Application Scenarios
The 11KV Indoor vacuum Load Break Switch is widely used in:
Power Distribution Systems
Ring main units (RMU)
Medium-voltage switchgear panels
Industrial Facilities
Factories and processing plants
Mining and petrochemical systems
Infrastructure Projects
Commercial buildings
Substations and urban grid networks
Why Choose Wzonpa
More compact than traditional air or oil switches
Maintenance-free vacuum interrupter design
Higher safety with integrated interlocking system
Better adaptability for modern smart grid systems
The 11KV Indoor vacuum Load Break Switch offers improved reliability and operational safety compared to conventional switching devices.
Appearance and installation dimensions
Technical parameters
SN
Item
Unit
Parameters
FZN25-12D/T630-20
FZRN25-12D/T125-31.5
1
Rated voltage
KV
12
2
Rated frequency
Hz
50
3
Rated current
A
630
125
4
Rated
Insulation level
1-minute power frequency withstand voltage
KV
Arc extinguishing chamber fracture 30; To the ground, alternating 42;Isolation fracture 48
Lightning impulse withstand voltage
KV
Ground to ground, alternating 75; |solation fracture 85
5
Rated dynamic stability current(peak value)
KA
50
6
4S thermal stability current
KA
20
7
Rated Active load breaking current
A
630
125
8
Rated closed-loop breaking current
A
630
125
9
Rated cable charging breaking current
A
10
10
10
Disconnect the capacity of the no-load transformer
KVA
1250
1250
11
Rated short-circuit breaking current
KA
31.5
12
Rated transfer current, rated handover current
A
2000
13
Fuse model
SDLAJ-12 SFLAJ-12
14
Impactor output energy
J
2-5(medium)
15
Rated short-circuit closing current
KA
50
16
Rated dynamic stability current of grounding switch
KA
50
17
Grounding switch 2S thermal stability current
KA
20
18
Rated voltage of auxiliary circuit
V
AC/CD 220;110
19
Mechanical lifespan
Times
10000
FAQ
Q1: What applications is this switch mainly used for?
A: It is commonly installed in indoor medium-voltage switchgear such as ring main units and distribution panels to manage load switching and circuit isolation.
Q2: Can it operate under frequent switching conditions?
A: Yes, the vacuum interrupter and spring mechanism are designed to handle repeated operations with stable performance and minimal wear.
Q3: What makes the vacuum interrupter more reliable?
A: Vacuum provides rapid dielectric recovery, ensuring arcs are extinguished quickly without residue, reducing wear and maintenance needs.
Q4: How is operational safety ensured during use?
A: The built-in mechanical interlocking system prevents incorrect operations, ensuring safe switching sequences and grounding procedures.
Q5: What environments can it be installed in?
A: I t is suitable for indoor installations with controlled temperature, humidity, and non-corrosive conditions as specified.
For inquiries about switchgear, MV soft starter, surge protective device or price list, please leave your email to us and we will be in touch within 24 hours.
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Privacy Policy