Products
33KV Outdoor SF6 Circuit Breaker
  • 33KV Outdoor SF6 Circuit Breaker33KV Outdoor SF6 Circuit Breaker
  • 33KV Outdoor SF6 Circuit Breaker33KV Outdoor SF6 Circuit Breaker
  • 33KV Outdoor SF6 Circuit Breaker33KV Outdoor SF6 Circuit Breaker
  • 33KV Outdoor SF6 Circuit Breaker33KV Outdoor SF6 Circuit Breaker

33KV Outdoor SF6 Circuit Breaker

Engineered with SF6 arc-quenching, a compact porcelain column, and a CT14 spring mechanism, Wzonpa factory's 33KV outdoor SF6 circuit breaker delivers fast interruption, strong insulation recovery, and low maintenance for reliable grid safety in harsh outdoor environments.
Rating: 5.0
(Rating Count: 1)

The 33KV Outdoor SF6 Circuit Breaker from Wzonpa, a professional China manufacturer, supplier, and factory, is engineered for medium-to-high voltage power transmission systems requiring stable interruption performance and long service life. It is designed with a compact porcelain column structure and CT14 spring operating mechanism, ensuring safe operation in harsh outdoor environments while maintaining high mechanical reliability and low maintenance demand.


Key Advantages

High breaking reliability: Stable arc extinction using SF6 gas ensures safe interruption under high load conditions.

Long mechanical lifespan: More than 3000 operating cycles for long-term grid stability.

High-accuracy CT integration: Amorphous alloy current transformer with 0.2/0.2S accuracy level.

Compact structure design: Easy installation and commissioning in substations and outdoor grids.

Low maintenance cost: SF6 insulation system reduces operational wear and service frequency.


Technical Highlights

The 33KV Outdoor SF6 Circuit Breaker adopts SF6 gas as arc-quenching medium, offering superior dielectric recovery performance. It can safely interrupt unloaded transmission lines up to 50 km without re-ignition risk. The spring operating mechanism ensures fast response, with opening time ≤0.06s and closing time ≤0.1s, supporting reliable grid protection under fault conditions.


Applications

The 33KV Outdoor SF6 Circuit Breaker is widely applied in:

Power generation plants and transmission substations

Industrial and mining power distribution networks

Rural and regional grid expansion projects

Outdoor air-insulated and hybrid substations

Its stable insulation performance ensures reliable operation even in high-altitude and extreme temperature regions.


Comparison & Competitive Advantages

Compared with oil or vacuum-based interrupters, the 33KV Outdoor SF6 Circuit Breaker provides:

Stronger arc extinguishing capability under high voltage stress

Lower operational noise and improved environmental adaptability

Reduced maintenance requirements over long service cycles

Higher insulation recovery speed after current interruption


Appearance and installation dimensions


Technical parameters

Item Unit Parameters
Rated voltage KV 40.5
Lightning impulse withstand voltage(peak value) KV 185
Rated insulated level          1-minute power frequency withstand voltage KV 95
Rated current A 2000
Mechanical lifespan Times 3000
Rated pressure of sulfur hexafluoride gas(gauge pressure at 20℃) Mpa 0.5
Alarm pressure/minimum functional pressure(gauge pressure at 20℃) Mpa 0.47/0.45
Rated short-circuit breaking current 40
Rated short-circuit making current(peak) KA 100
Rated short-time withstand current(thermal stability current) 40
Rated peak withstand current(dynamic stability current) KA 100
Rated out of step breaking current KA 10
Accumulated breaking times under rated short-circuit breaking current Times 12
Rated short-circuit duration S 4
Closing time(at rated operating voltage) S ≤0.1
Opening time(at rated operating voltage) S ≤0.06
Rated operating sequence A 0-0.3S-CO-180S-CO
Rated opening and closing current of a single capacitor bank 400
Annual gas leakage rate % ≤1
Moisture content of sulfur hexafluoride gas (VV) ≤150x10-6
Rated operating voltage for CT14 type spring operated mechanism
Voltage of closing coil and opening coil V AC:220      380    DC:48    110        220
Energy storage motor voltage V AC:220     380     DC:110          220
Weight of sulfur hexafluoride gas kg 8
Weight of circuit breaker(including operating mechanism) kg 1400


Item    Unit Parameters  Technical requirement
Moving contact stroke mm 95±2 Measure the travel of the moving contact
Contact opening distance mm 60±1.5 Measure the distance between the dynamic and static arc heads
Periodic closing between poles M/S ≤3 Measure the difference in distance between the dynamic and static arc contacts
Synchronization of inter pole opening M/S ≤2 Measure the difference in distance between the dynamic and static arc contacts
Main circuit resistance mΩ ≤120 Direct charging voltage drop method for measurement,with current passing through
during measurement
Closing speed M/S 3.2±0.2 Rated air pressure and measurement method
Opening speed M/S 3.4±0.2 Customer specific air pressure and measurement method
Closing with slow stroke mm 10+1.5 In the closed state
Positioning room for closing buffer mm 1~2 In the closed state
Part 48.6kV PC 20 Measure with a partial discharge meter at rated pressure,apply a voltage of 48.
6kV to both output terminals of the circuit breaker,hold for 1 minute for
measurement,and then reduce the voltage to 28kV for measurement
Discharge 28kV PC 10


FAQ

Q1: Why is SF6 gas used in this breaker?

A: SF6 gas has strong electronegativity and excellent arc-quenching ability, allowing rapid electron absorption and fast dielectric recovery after interruption.


Q2: What environments can the 33KV Outdoor SF6 Circuit Breaker operate in?

A: It is suitable for high-altitude areas up to 3000m, temperatures from -40°C to +40°C, and environments without heavy pollution or corrosive gases.


Q3: How reliable is the mechanical performance?

A: The breaker supports over 3000 mechanical operations, ensuring long-term durability in frequent switching conditions.


Q4: What makes Wzonpa’s product different from others?

A: The 33KV Outdoor SF6 Circuit Breaker combines high-precision CT integration, compact design, and stable SF6 insulation performance, ensuring higher operational safety and efficiency compared to conventional solutions.


Product show

Send Inquiry
Contact Info
  • Address

    No. 58 Binhainan Fourth Road, Economic Development Zone, Yueqing City, Wenzhou City, Zhejiang Province, China

For inquiries about switchgear, MV soft starter, surge protective device or price list, please leave your email to us and we will be in touch within 24 hours.