Buy quality 11KV Vacuum Circuit Breakers Vacuum CKT Breaker from leading China manufacturer. It is designed for medium-voltage outdoor power distribution systems with stable arc-extinguishing performance and reliable insulation in harsh environments. Using SF6 gas as the insulating and breaking medium, it ensures strong dielectric strength, fast fault interruption, and low maintenance operation. Suitable for substations, industrial grids, and utility networks, this equipment supports frequent switching and short-circuit protection.
Wzonpa factory’s 11KV Vacuum Circuit Breakers Vacuum CKT Breaker is an indoor medium-voltage switching device designed for 12kV, 50Hz three-phase power systems. It is used for protection and control in distribution networks, offering reliable interruption of load current, short-circuit current, and capacitor bank switching. As a China manufacturer, Wzonpa develops this product with standardized VS1-12 side-mounted structure, making it suitable for integration into various switchgear systems. As a professional supplier and factory source, Wzonpa provides consistent design compatibility for industrial, commercial, and utility power applications.
Product Structure and Design
The 11KV Vacuum Circuit Breakers Vacuum CKT Breaker adopts a fixed installation, side-mounted VS1-12 structure, mainly used in fixed switchgear cabinets.
Main components include:
Vacuum interrupter chamber (core breaking unit)
Spring energy storage operating mechanism (manual or electric)
Three-phase conductive system
Insulation support structure and frame assembly
This configuration supports stable operation under frequent switching conditions and ensures compatibility with ring main units (RMUs), box-type substations, and customized distribution systems.
Application Scope and System Integration
This hot sale 11KV Vacuum Circuit Breakers Vacuum CKT Breaker is widely used in medium-voltage distribution and control systems across multiple industries.
Typical applications:
Industrial and mining power distribution systems
Commercial building electrical networks
Substations and utility grid systems
Renewable energy grid integration points
As a vacuum circuit breaker supplier solution in China, Wzonpa 11KV Vacuum Circuit Breakers Vacuum CKT Breaker is suitable for transformer protection, feeder circuits, motor control, and capacitor switching operations. It can be integrated into standard switchgear panels and non-standard power distribution systems.
Operating Conditions and Environmental Requirements
This equipment is designed for indoor medium-voltage environments with controlled installation conditions.
Operating conditions:
Ambient temperature: -15°C to +40°C
Altitude: ≤1000 m (higher altitude requires insulation adjustment)
Relative humidity: daily ≤95%, monthly ≤90%
Seismic intensity: ≤ Level 8
Environment: no explosive gas, chemical corrosion, or severe pollution
The design ensures reliable performance in typical distribution environments such as substations and industrial facilities.
Mechanical and Operational Characteristics
The breaker is engineered for stable mechanical coordination and fast switching response.
Key operational features:
Contact opening distance: 11 ± 1 mm
Average opening speed: 1.1 ± 0.2 m/s
Average closing speed: 0.6 ± 0.2 m/s
Opening time: ≤0.1 s
Phase difference during operation: ≤2 ms
Main circuit resistance: ≤60 μΩ
These parameters support consistent switching behavior and long mechanical endurance in repeated operations.
Appearance and installation dimensions
Technical parameters
SN
Item
Unit
Parameter
1
Rated voltage
kV
12
2
Rated frequency
Hz
50
3
Rated current
A
630~1250
1250
1250
4
Rated short-circuit breaking current
kA
20
25
31.5
5
Rated short-circuit making current
kA
50
63
80
6
Rated short-circuit making current(peak)
kA
50
63
80
7
4S rated short-circuit withstand current
kA
20
25
31.5
8
Rated insulated level
Power frequency withstand voltage (before and after rated breaking) Impact withstand voltage(before and after rated breaking)
kA
42(fracture 48)
75(fracture 85)
9
Rated operating sequence
O-0.3S-CO-180S-CO
10
Mechanical lifespan
Times
10000
11
Rated short-circuit breaking current breaking times
Times
50
12
Rated closing voltage of operating mechanism(DC)
V
110,220
13
Rated opening voltage of operating mechanism(DC)
V
110,200
14
Contact opening distance
mm
11±1
15
Overtravel(compression length of contact spring)
mm
3.5±0.5
16
Three phase opening and closing bounce time
ms
≤2
17
Contact closing bounce time
ms
≤2
18
Average opening speed
m/s
1.1±0.2
19
Average closing speed
m/s
0.6±0.2
20
Opening time
Under the highest operating voltage
≤0.05
At the lowest operating voltage
s
≤0.08
21
Closing time
s
0.1
50
22
Main circuit resistance of each phase
uΩ
60
23
Allowable wear and accumulated thickness of dynamic and static contacts
mm
3
FAQ
Q1: What systems can this vacuum circuit breaker be used in?
A: The 11KV Vacuum Circuit Breakers Vacuum CKT Breaker is suitable for 12kV distribution systems, including substations, RMUs, industrial networks, and compact substations.
Q2: Can it handle frequent switching operations?
A: Yes. The vacuum interrupter and spring mechanism design support repeated operation under rated current conditions.
Q3: What installation type is used?
A: It uses a fixed, side-mounted VS1-12 structure designed for indoor switchgear panels.
Q4: Is it suitable for outdoor use?
A: This model is designed for indoor environments. Outdoor use requires additional protective enclosure systems.
For inquiries about switchgear, MV soft starter, surge protective device or price list, please leave your email to us and we will be in touch within 24 hours.
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Privacy Policy